Location:Home > Products > DDC building automation system > DDC control system for air handling units
    classification:

    DDC control system for air handling units

    System uses the DDC control to control the air conditioning unit, consisting of air valve, filter, cooler, heater,heating coil fan. The components of the control system is composed of air temperature and humidity transmitter, temperature transmitter, return air temperature and humidity transmitter, antifreeze switch, pressure switch, air valve actuator, electric control valve.

    DDC control system for air handling units

     

    Composition:

    System uses the DDC control to control the air conditioning unit, consisting of air valve, filter, cooler, heater,heating coil fan. The components of the control system is composed of air temperature and humidity transmitter, temperature transmitter, return air temperature and humidity transmitter, antifreeze switch, pressure switch, air valve actuator, electric control valve.

    Monitor and control function:

    The electric air valve, electric control valve and the blower fan interlock, when activated, fresh air valve to open(0-100% can be set), return air valve opening (can be set to 0-100%) electric control valve according to the PID Festival opened; the blower stops, electric, air valve, electric regulating valve is closed at the same time.

    But when the filter is blocked, the pressure switch filter blocking alarm signal is given.

    The winter when the coil temperature is too low, low temperature freezing switch gives a switch signal, the fanstops running, the air valve is closed, the electric control valve to open, in order to prevent the coil. When thefrost preventive switch back to normal, re start the fan, open the air valve, the unit back to work.

    Temperature control air conditioning unit according to the deviation of the most return air temperature and airtemperature, the opening degree of PID by regulating water road, electric control valve, so that the measuredtemperature reaches the set temperature value.

    Humidity control air conditioning unit according to the air humidity and air humidity test set error, opening byPID regulating steam electric valve, so that the measured temperature reaches the set temperature value.

    The fan monitoring and control for the monitoring of fan operation status, fault and hand / automatic control ofair blower, the start and stop.

    This figure of the humidification for dry steam humidizer selection, so the amount of steam electric valve andcontrol humidification, humidification for water, do not use electric regulating valve control device, but directlycontrol humidifier, generally for the state monitoring, control the start and stop.

    组成:
          本空调机组控制系统采用DDC 控 制,由新风阀、初效过滤器、表冷器 加热盘管、加温器、送风机组成??刂葡低车南殖≡尚路缥率缺渌推?、回风温度变送器、送风温湿度变送器、防冻开关、压差开关、风阀执行器、电动调节阀组成。
    监控与控制功能:
    ※电动风阀、电动调节阀与送风机联锁,当送风机启动时,新风风阀开启至(0-100%可设定),回风风阀开启至(0-100%可设定)电动调节阀按P ID 调 节开启;送风机停止时,电动、风阀、电动调节阀同时关闭。
    ※当过滤器阻塞时,压差开关给出过滤器堵塞报警信号。
    ※当冬季盘管温度过低时,低温防冻开关给出开关信号,风机停止运行,新风阀关闭,电动调节阀打开,以防止盘管冻裂。当防冻开关恢复正常时,重新启动风机,打开新风阀,机组恢复工作。
    ※空调机组温度控制为根据回风实测温度与回风设定温度的偏差,按PID 调 节水路电动调节阀的开度,使实测温度达到设定温度值。
    ※空调机组湿度控制为根据送风实测湿度与送风设定湿度的偏差,按PID 调 节汽路电动调节阀的开度,使实测温度达到设定温度值。
    ※送风机的监测与控制为监测送风机的运行状态,故障状态和手/ 自 动状态,控制送风机的启停。
    ※本图中的加湿方式为干蒸汽加湿,故选用电动调节阀又控制加湿的蒸汽量,如为水加湿,不选用电动调节阀,而是直接控制加湿器的控制设备,一般为监测其状态,控制其启停。

    冷冻站机组DDC控 制

    冷冻站由2 台 冷水机组、3 台 冷冻水循环泵、 2 台 冷却塔及分集水器等组成??刂葡低车南殖≡涠乘┗厮露却衅?,冷冻水供回水压差传感器,冷冻水供水流量计,水流开关,冷却水供回水温度传感器,冷水机组冷冻水电动蝶阀,冷却水电动蝶阀、冷却塔冷却水进口电动蝶阀和压差旁通阀组成。

    监测与控制功能:

    ※冷水机组的监测:因现有冷水机组基本均带有以微机处理器为核心的单位控制器, 在 本系统中按单元控制器与楼宇自控系统直接通信
    的 方案, 未 考虑其占用1/0 点 。根据不同情况,也可以采用由冷水机组提供检测的干节点,控制系统对此进行监测和控制的方案,应根
    据 现场情况确定。
    ※监测冷冻水供回水温度,以了解冷冻水的工作温度是否在合理的范围之内。
    ※监测冷冻水供回水压差,根据供回水压差,调节压差旁通阀的开度。
    ※监测冷冻水供水流量,与冷冻水供回水温差相结合,可计算出冷量,以此作为能源消耗计量的依据。
    ※监测冷却水供回水温度,以了解冷却水的温度是否在合理的范围之内。
    ※冷冻水循环泵,冷却水循环泵,冷却塔风机监测与控制点为:运行状态反馈、故障状态反馈、手/ 自 动反馈、水泵启??刂坪捅淦悼刂?(反馈数量可根据实际工程需要决定),循环泵与风机可根据现场情况进行启??刂?。
    ※冷却塔进水管的电动阀一般采用电动蝶阀,用于当冷却塔停止运行时切断水路,以防短路,同时可适当调整进入各冷却塔的进水量,使 其分配均匀,以保证各冷却塔都能达到最大使用工况。
    ※冷水机组冷冻侧与冷却侧的阀门均采用电动蝶阀, 用 于当冷水机组停止运行时切断水路,以防水流短路。
    ※群控功能:根据冷冻水供回水温度与流量,计算出空调系统的实际负荷,将计算结果与当时冷水机组投运台数下的总供冷量作比较,若 空调系统的实际负荷小于一台冷水机组的供冷量时,则发出停止一台冷水机组的运行提示,管理人员确认后停止该机组运行。冷水机组停止运行后,则其相应的冷却塔、冷冻水泵和冷却水泵停止运行。

     